TR302-304 A / B -TDxxx - TK301 / 302 - WKT3xxR / xxF - WHT390 - TU4xx
6 6T 7871a
■ Channel function: Shutters / blinds, Up / Down - Shutters / blinds, Up - Shutters / blinds, Down
• Shutters / blinds, Up / Down:
- This function is used to control a rolling shutter or a blind with a single button (Input). Change of function after each
operation (Down, STOP, Up, STOP). Slat angle adjustment is not possible here.
• Shutters / blinds, Up:
- This function controls shutters or blinds using two push buttons (Inputs). Emission of the Up control when the input
contact closes (or when the push button is pressed) and emission of the Slat angle / Stop object (short key-press).
• Shutters / blinds, Down:
- This function controls shutters or blinds using two push buttons (Inputs). Emission of the Down control when the
input contact closes (or when the push button is pressed) and emission of the Slat angle / Stop object (short key-
press).
■
Channel function: 1-button dimmer
This function allows ON / OFF or Increase / Decrease controls using one push button.
There are 2 different function types: 1-button dimmer, 2-button dimmer.
■
Channel function: Shutters / blinds, Alarm 1 - Shutters / blinds, Alarm 2
The Alarm 1 and Alarm 2 functions allow alarms coming from automatic controls to be periodically emitted (anemometer, Rain
detector, Light-sensitive switch, etc.).
To place the shutters in safety position in case of bad weather: link the Alarm 1 and Alarm 2 functions with the Alarm 1 and
Alarm 2 object of the Shutter / Blind output modules.
These functions have the highest priority. Alarm 1 has a higher priority than Alarm 2.
■
Channel function: Heating, Comfort / Eco - Heating, Comfort - Heating, Eco - Heating, Frost protection - Heating,
Absence / - - Heating, Auto / - - Heating, Frost protection / -
This function is used select a heating setpoint.
The operating modes are sent via the Set point selection object.
■ Channel function: Heating ON / OFF
Emission of the OFF control when the input contact closes (or when the push button is pressed) and emission of the ON control
when the input contact opens (or when the push button is released).
■
Channel function: Lighting, Priority ON - Lighting, Priority OFF - Shutters / blinds, Up priority - Shutters / blinds,
Down priority - Heating, Comfort priority - Heating, Night set-point priority
This function sends priority-start or priority-stop commands. No other command is taken into account if a priority is active. Only
end of priority or alarm commands will be taken into consideration. The value of the Priority object is defined when the channel
function is selected.
■
Channel function: Scene 1 to 8
The Scene function sends group controls to different kinds of outputs to create ambiences or scenarios. (Panic switch,
Television,etc.).
The value of the Scene object is defined when the channel function is selected.
■
Channel function: Lighting, Timer - Heating, Timer
This function operates like a staircase light function. The controls are sent on the bus via the Timer object.
Feature:
short key-press (Rising edge): Timer start.
long key-press (Falling edge): Timer end.
NB: The timer duration is set on the output module.
3. Main characteristics
Product TR302 A / B TR304 A / B TDxxx TK301 / 302 WKT3xxR WYT3xxF WHT390 TU4xx
Max. number
of group
addresses
13 25 13 / 25 / 37 4 / 7 13 / 25 / 37 13 / 25 / 37 13 / 25 / 37 32
Max. number
of links
13 25 13 / 25 / 37 4 / 7 13 / 25 / 37 13 / 25 / 37 13 / 25 / 37 50
Parameters
2 4 2 / 4 / 6 1 / 2 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 / 18
Objects
3 5 3 / 5 / 7 3 / 5 3 / 5 / 7 3 / 5 / 7 3 / 5 / 7 3 / 5 / 7 / 19
Kommentare zu diesen Handbüchern